Summary of Predictor-Corrector Procedure

The predictor-corrector scheme can be summarized as follows:

  • Using Equation eq:SteadyStateSystemOutput, an estimate is made of the air system energy required to balance the equation with the zone air temperature equal to the setpoint temperature.

  • With that quantity as a demand, the air system is simulated to determine its actual supply capability at the time of the simulation. This will include a plant simulation if necessary.

  • The actual air system capability is used in Equation eq:ZoneTemperatureUpdateEquation to calculate the resulting zone temperature.